Liebert® GXT3, 700VA -3000VA Models
Reliable On-Line UPS Protection In A Compact 2U Package
Liebert GXT3 is a full feature UPS providing reliable protection for IT network equipment and data centers. It is a true on-line UPS that delivers continuous, high-quality AC power to IT equipment with no break when transferring to battery. It protects equipment from virtually all power disturbances due to blackouts, brownouts, sags, surges or noise interference. The UPS is available in rack/tower configurations.
Click here for Liebert GXT3 5-10kVA Models |
|
|
Features and Benefits
- On-line design means zero transfer time from external to internal power. When utility power fails, your critical load remains supported by a seamless flow of power.
- Liebert GXT3 rated output power factor of 0.9 better matches up with switch-mode power supplies used in today’s IT equipment. A higher output power factor allows for a more efficient utilization of the UPS.
- The UPS provides easy serviceability with user replaceable hot-swappable batteries.
- For maximum control, Liebert GXT3 is custom configurable to your needs using a specially designed Windows software package.
|
The Liebert GXT3 is ideally suited for:
- Data Centers
- Network Computers
- VoIP
- Network Closets
- Servers
- Large Network Peripherals
- Network Storage Devices
|
|
|
What's in the Box?
- Power factor correction
- Internal batteries
- Frequency conversion
- Internal automatic bypass to utility in case of adverse UPS conditions
- Manual bypass capability
- Support for up to four external battery cabinets (rack/tower models)
Parts

|
|
Technical Specifications

|
|
Frequently Asked Questions
What is GXT3?
- Liebert GXT3 is the latest On-Line UPS product for servers and networking devices. It replaces existing the Liebert GXT2.
- It is global product available in 120V and 230V.
- Liebert GXT2 700-3000VA will be discontinued from Nov 2009 onwards.
- Liebert GXT2 4500-10000VA are still available.
How does Liebert GXT2 differ from Liebert GXT3?
|
Features
|
GXT 3G
|
GXG 2G
|
|
Output PF
|
0.9
|
0.7
|
|
Input PF
|
0.99
|
0.97
|
|
Input Protection
|
Circuit Breaker
(700-300VA)
|
Fuse (700-1500VA)
Circuit Breaker (2000-3000VA)
|
|
Input THDi
|
5%
|
8%
|
|
AC - AC Efficiency
|
90%
|
87%
|
|
Audible Noise
|
< 48dBA
|
< 55dBA
|
|
Recharge Time
|
3 hours to 90%
|
5 hours to 95%
|
|
Overload1
|
105% to 125% - 60 seconds
125% to 150% - 50 seconds
150% to 200% - 2 seconds
>200% - 250ms
|
112% to 130% - 10 seconds
130% to 200% - 2 seconds
>200% - 96ms
|
|
Full-Load
Low Line Transfer
|
176VAC (192VAC for 3000model)
|
176VAC
|
Runtime Comparison between Liebert GXT2 and Liebert GXT3
|
(minutes)
|
700VA
|
1000VA
|
1500VA
|
2000VA
|
3000VA
|
|
GXT2 (PF 0.7)
|
17
|
11
|
7
|
6
|
5
|
|
GXT3 @ PF 0.7
|
11
|
8
|
8
|
6
|
5
|
|
GXT3 @ PF 0.9
|
11
|
4
|
4
|
4
|
4
|
|
|
|
|
|
|
|
|
700VA
|
1000VA
|
1500VA
|
2000VA
|
3000VA
|
|
GXT2
|
4x12Vx7.24AH
|
4x12Vx7.2AH
|
4x12Vx7.2AH
|
4x12Vx9AH
|
6x12Vx9AH
|
|
GXT3
|
4x12Vx5AH
|
4x12Vx5AH
|
4x12Vx7.2AH
|
4x12Vx9AH
|
6x12Vx9AH
|
How does a UPS with higher power factor benefit users?
- UPS is rated both in VA and Watts. Exceeding the specified VA or Watts will cause the UPS to overload.
- Modern servers and networking devices are equipped with Power Factor Corrected (PFC) power supply, whose pf is as high as 0.98. It means if power supply is rated at 100VA, it is also rated at 98W.
- UPS’s with 1000VA/900Watts can support nine (9) of such devices. UPS’s with 1000VA/700Watts can only support seven (7) of such devices.
Can Liebert GXT3 have additional USB or RS232 port?
- No. Liebert GXT3 has one (1) USB, (1) any mode shutdown, (1) battery mode shutdown, on battery / low battery relays, and one (1) Liebert Intellislot out-of-box. There is no optional card with ports.
Is Liebert IS-WEBCARD compatible with Liebert GXT3?
Can the Micropod for Liebert GXT2 be used with Liebert GXT3?
- YES. The Part Number of Liebert Micropod remains unchanged. All existing Micropods can be used with Liebert GXT3.
Can the battery cabinets of Liebert GXT2 be used with Liebert GXT3?
- NO. Battery cabinets for Liebert GXT2 and Liebert GXT3 are NOT interchangeable.
What is the warranty of Liebert GXT3?
- Standard UPS warranty (usually 2 years) applies.
What sets Liebert GXT3 apart from competition?
- High Power Factor in All Models
▪ PF 0.9 in all 5 ratings while only Eaton 9130 offers PF0.9 under on-line double conversion UPS
-
Rack/Tower Convertible in Slim size
▪ Convenient rack/tower in 2U design. Slim 2U compact design
▪ Rotatable front panel
-
Small footprint and light weight
-
Micropod bypass switch increases availability
Click here for Liebert GXT3 5-10kVA Models
|
|
|