Overload Capability
 

  • Customer Benefits: Greater Uptime & Peace-of-mind design
  • Advanced DSP control
    • Low voltage distortion output waveform
    • Inverter
    • 100 – 110%, 1hour
    • 110 – 125%, 10min
    • 125 – 150%, 1min
    • Bypass
    • 100 – 135% Continuous
    • 135 – 170% 10min
    • 1000% 100ms 
 

Reliability
Self-diagnosis and Digital Calibration
 

  • Customer Benefits: Customer Benefits:  Increased uptime through minimizing human intervention
  • Self-diagnosis monitoring
    • Real time inverter/rectifier status
    • Real time battery capacity and status
    • Real time operation temperature
    • Hot-plug fans and individual fan failure alarm
  • Digital Calibration
    • Precise voltage/current display readings are software calibrated
    • Programmable set points in place of conventional calibration potentiometers

Back   Next