Updating...
|
|
Overload Capability
|
- Customer Benefits: Greater Uptime & Peace-of-mind design
- Advanced DSP control
- Low voltage distortion output waveform
- Inverter
- 100 – 110%, 1hour
- 110 – 125%, 10min
- 125 – 150%, 1min
- Bypass
- 100 – 135% Continuous
- 135 – 170% 10min
- 1000% 100ms
|
|

|
|
Reliability
Self-diagnosis and Digital Calibration
- Customer Benefits: Customer Benefits: Increased uptime through minimizing human intervention
- Self-diagnosis monitoring
- Real time inverter/rectifier status
- Real time battery capacity and status
- Real time operation temperature
- Hot-plug fans and individual fan failure alarm
- Digital Calibration
- Precise voltage/current display readings are software calibrated
- Programmable set points in place of conventional calibration potentiometers
|
|
|
|
|
|
|
|